3-Phase Power Quality Recorder
The Fluke 1750 is a 3-Phase Power Quality Recorder and record every power quality paramater, every cycle, all the time.
It offers easily record three-phase power quality and monitor for power quality disturbances.
Common Applications:
Long-term analysis: Uncover hard-to-find or intermittent issues; monitor critical equipment, capturing power quality events to correlate with equipment malfunction
Power quality surveys: quantify power quality throughout a facility, documenting results with professional reports
Quality of service compliance: validate incoming power quality at the service entrance
Equipment Installation/Commissioning: Benchmark: power system prior to install to insure quality of Service
Internal memory capacity for data: 2 GB
Maximum recording period: 31 days
Measurement time control: automatic
Power requirements: 100 to 240 V rms +/-10%, 47-63 Hz, 40 W
Voltage and current measurements:
Voltage measurement range:
AC: +/- 1000 V rms + 10% over range
DC: +/- 1000 V + 10% over range
Voltage crest factor: 3 or less
Current measurement range: depends on current probe used
Current crest factor: 4 or less
Measurement types:
One Phase Plus Neutral, One Phase IT No Neutral, One Phase Split Phase, Three Phase Wye, Three Phase Delta, Three Phase IT, Three Phase High Leg, Three Phase Open Leg, 2 Element Delta, 21/2 Element Wye
Input channels Voltage: 4 channels, AC/DC
Current: 5 channels
Voltage channels Input resistance: 2 Mohms
Input capacitance: < 20 pF
Current input characteristics 2 V rms = full scale, 1 Mohms input impedance for ferro CTs, low impedance for Flexi-CTs
Measuring method: Simultaneous digital sampling of voltage and current. Digital PLL synchronized sampling, internal frequency reference used during voltage drops.
All measurements comply with IEC61000-4-30 standards for correct evaluation of all measured values including voltage, current, power, harmonics, flicker etc.
Quick and reliable configuration: ARCHOS 43 Internet Tablet
Threshold-free set up: Apply thresholds after data is collected with Fluke Power Analyze Software
Cross-channel and current triggering capture every measurement, on every channel, every time
Easily analyze data and generate reports with automated EN50160 reporting and compliance
Auto Report creates either standard reports or customized reports with the minimum effort or hassle
Set up in minutes with self-identifying current probes and single-lead voltage connections
No need to reconnect wires: Swap channels internally with the wireless PDA or PC when connections are not correct
Measure parameter: Voltage and current on three phases, neutral, and ground
5 MHz, 8000 Vpk waveform capture: Get a detailed picture of even the shortest events
Quickly retrieve data: With included SD memory card or via the 100 BaseT high-speed Ethernet connection. SD card includes automatic download to SD when no other connection is made to the Instrument
Dimensions: 215 x 310 x 35 mm
Weight: 6.3 kg
€ 8,790 (net) $11,075 (US)